RHH Or RHW, EPR/XLPO, 600 Volt

RHH Or RHW, EPR/XLPO, 600 Volt

Supplying you with customized rhh or rhw, epr/xlpo, 600 volt, it is one of the reliable rhh or rhw, epr/xlpo, 600 volt manufacturers and suppliers, welcome to wholesale our products at good price from our factory. UL Industrial Cables RHH or RHW, EPR/XLPO, 600 Volt Cable Parameter

Product Details

Supplying you with customized rhh or rhw, epr/xlpo, 600 volt, it is one of the reliable rhh or rhw, epr/xlpo, 600 volt manufacturers and suppliers, welcome to wholesale our products at good price from our factory.

UL Industrial Cables RHH or RHW, EPR/XLPO, 600 Volt

Application and Description

600 Volt EPR/XLPO Type RHH or RHW-2 or USE-2 is suited for use in mass transit and general industry applications where flexibility, fire resistance, and low smoke generation are concerns. May be installed in wet or dry locations (including direct burial for size AWG 8 and larger) in cable trays or in raceways. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload conditions, and 250°C for circuit conditions.

Cable Construction

Conductor

Class B compressed concentric stranded bare copper in accordance witd ASTM B3 and B8 and ICEA.

Insulation/Jacket

Being resistant to moisture, most oils, acids, and alkalies EPR (ethylene propylene rubber) insulation.  Jacket: Flame retardant, moisture and sunlight resistant XLPO.

Color

upon request, black is preferable

Technical Characteristics

- UL 44 - Thermoset-Insulated Wires and Cables
- UL 1581 - UL Flame Exposure Test (VW-1)
- UL 1685 - UL Flame Exposure Test
- ICEA S-68-516 (NEMA WC8)
- RoHS

Cable Parameter

AWG OR KCMIL

STRAND

NOMINAL INSULATION THICKNESS INCH/MM

NOMINAL JACKET THICKNESS INCH/MM

NOMINAL OVERALL DIAMETER INCH/MM

CABLE WEIGHT

LBS/KFT KG/KM

2

7

0.045

1.14

0.030

0.76

0.445

11.3

250

372

1

19

0.055

1.40

0.045

1.14

0.524

13.3

335

499

1/0

19

0.055

1.40

0.045

1.14

0.563

14.3

410

610

2/0

19

0.055

1.40

0.045

1.14

0.607

15.4

503

749

3/0

19

0.055

1.40

0.045

1.14

0.657

16.7

673

921

4/0

19

0.055

1.40

0.045

1.14

0.713

18.1

764

1137

250

37

0.065

1.65

0.065

1.65

0.838

21.3

940

1399

350

37

0.065

1.65

0.065

1.65

0.944

24.0

1274

1896

500

37

0.065

1.65

0.065

1.65

1.076

27.3

1769

2633

750

61

0.080

2.03

0.065

1.65

1.291

32.8

2616

3893

1000

61

0.080

2.03

0.065

1.65

1.445

36.7

3428

5101