Universal Cables Limited
Categories
Contact Us

Universal Cables Limited

Shandong Factory
High-Tech Zone, Zhangqiu, Jinan City, China
Tel:+86 531-83689222
Fax:+86 531-83689444

Kunshan Factory
268, Huangpu River Road, Dianshanhu Town, Hunshan City, China
Tel:+86 512-57429205
Fax:+86 512-57429201

Sales office

Tel:+86 531-88817113
Fax:+86 531-88819113
E-mail:inquiry@uecable.com
Web Site:www.ue-cable.com

XLPE Insulated, LSZH Sheathed, Overall Screened And Armoured Instrumentation Cables (Single Triple)

XLPE Insulated, LSZH Sheathed, Overall Screened And Armoured Instrumentation Cables (Single Triple)

Supplying you with customized xlpe insulated, lszh sheathed, overall screened and armoured instrumentation cables (single triple), it is one of the reliable xlpe insulated, lszh sheathed, overall screened and armoured instrumentation cables (single triple) manufacturers and suppliers, welcome to...

Product Details

Supplying you with customized xlpe insulated, lszh sheathed, overall screened and armoured instrumentation cables (single triple), it is one of the reliable xlpe insulated, lszh sheathed, overall screened and armoured instrumentation cables (single triple) manufacturers and suppliers, welcome to wholesale our products at good price from our factory.

XLPE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Single Triple)

RE-2X(St)HSWAH 70°C / 300 V

STANDARDS

Basic design to EN 50288-7

APPLICATION

Instrument cable minimizes noise and signal interference, delivering clean signals in harsh environments and general manufacturing operations.

FIRE PERFORMANCE

Flame Retardance (Single Vertical

Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE

0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation

(Vertically-mounted bundled wires

& cable test)***

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*

Minimum Smoke Emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

No Toxic gases

NES 02-713; NF C 20-454

Sunlight Resistance

UL 1581 section 1200

Oil Resistance**

ICEA S-73-532

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.

VOLTAGE RATING

300V

CABLE CONSTRUCTION


Conductor:

Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation:

Extruded cross-linked XLPE compound, EN 50290. 2-29.

Pair:

Two conductors twisted to form a pair

Lay-up:

Pairs laid up in layers of optimum pitch

Separator:

Polyester tape

Overall Screen:

Aluminium/polyester tape with tinned copper drain wire, 0.5mm2

Inner sheath:

HFFR compound, EN 50290-2-27

Armour:

Galvenized round steel wire, EN 10257-1

Outer Sheath:

Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

COLOUR CODE


Insulation:

Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.

Outer Sheath:

Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES


Temperature Range During Operation (Fixed State):

-30°C – +70°C

Temperature Range During Installation (Mobile State):

-5°C – +50°C

Minimum Bending Radius:

7.5 X Overall Diameter

CONSTRUCTION PARAMETERS

Cable

Code

RE-2X(St)HSWAH

No. of Triples x3xCross Section

Nominal Insulation Thick- ness

Nominal Inner Sheath Thick- ness

Nominal

Overall Diameter Over Inner Sheath

Nominal Armour Wire Diameter

Nominal Outer Sheath Thick- ness

Nominal Overall Diameter

Approx. Weight


No.x3xmm2

mm

mm

mm

mm

mm

mm

kg/km

RE-2X(St)HSWAH 1T0.5

1x3x0.50

0.35

0.8

5.4

0.9

1.3

9.8

200

RE-2X(St)HSWAH 1T0.75

1x3x0.75

0.38

0.9

6.1

0.9

1.3

10.5

220

RE-2X(St)HSWAH 1T1.0

1x3x1.0

0.4

0.9

6.6

0.9

1.3

11.0

244

RE-2X(St)HSWAH 1T1.3

1x3x1.3

0.45

0.9

7.2

0.9

1.3

11.6

268

RE-2X(St)HSWAH 1T1.5

1x3x1.5

0.45

0.9

7.5

0.9

1.3

11.9

293

Note : Other conductor sizes & core configurations are available upon request.

Electrical PROPERTIES

Conductor Area Size

mm 2

0.5

0.75

1.0

1.3

1.5

Insulation thickness (nominal)

mm

0.35

0.38

0.4

0.45

0.45

Conductor resistance (20°C)

Ω/km

36.7

25

18.5

14.2

12.3

Insulation resistance (20°C)

MΩ.km(Min.)

5000

Mutual Capacitance (1 kHz)

pF/m(Max.)

115

Capacitance unbalance(1 kHz)

pF/500 m (Max.)

500

Inductance

mH/km(Max.)

1

L / R (ratio) (max.)

μH/Ω

25

25

25

40

40

Operating voltage Urms

V

300

Test Voltage

Core to Core

V

1500

Core to Screen

V

1500


Related Products