600 1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables (Multicore)

600 1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables (Multicore)

Supplying you with customized 600 1000v xlpe insulated, pvc sheathed, armoured power cables (multicore), it is one of the reliable 600 1000v xlpe insulated, pvc sheathed, armoured power cables (multicore) manufacturers and suppliers, welcome to wholesale our products at good price from our...

Product Details

Conductor cross-sectional area

2-core cable d.c.

2 cables, single-phase a.c.

3 or 4 cables, 3-phase a.c.

2 cables, single- phase a.c.

3 or 4 cables, 3-phase a.c.

In ducts or in ground

In ducts or in ground

1

2

3

4

5

6

mm2

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

1.5

31.0

31.0

27.0

31.0

25.0

2.5

19.0

19.0

16.0

19.0

15.0

4

12.0

12.0

10.0

12.0

9.7

Supplying you with customized 600 1000v xlpe insulated, pvc sheathed, armoured power cables (multicore), it is one of the reliable 600 1000v xlpe insulated, pvc sheathed, armoured power cables (multicore) manufacturers and suppliers, welcome to wholesale our products at good price from our factory.

600/1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables (Multicore)

CU/XLPE/PVC 600/1000V Class 2

CU/XLPE/PVC/SWA/PVC 600/1000V Class 2

Application:

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.

STANDARDS:

Basic design adapted to IEC 60502-1; BS 5467

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)**

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)**

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.

Insulation: Extruded cross-linked XLPE compound.

Inner Sheath(optional): PVC Compound

Armouring(optional): Galvanized Steel Wire

Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation Colour as per BS7671


With Earth Conductor

Without Earth Conductor

2Cores

-

Brown, Blue

3Cores

Yellow/Green, Brown, Blue

Brown, Gray, Black

4Cores

Yellow/Green, Brown, Gray, Black

Brown, Gray, Black, Blue

5Cores

Yellow/Green, Brown, Gray, Black, Blue

Brown, Gray, Black, Blue, Black

Above 5 Cores

Yellow/Green, Black Numbered

Black Numbered

Sheath Colour: Black (other colors upon request)

Physical AND THERMAL PROPERTIES

Temperature range during operation: Max.90°C for XLPE

250°C in short-circuit for 5secs max.

Minimum bending radius: 8 x Overall Diameter (unarmoured cable)

10 x Overall Diameter (armoured cable)

CONSTRUCTION PARAMETERS

Conductor

Electrical Properties

Conductor Operating Temperature : 90°C

Ambient Temperature : 30°C

Current-Carrying Capacities (Amp)

No. of Core X Cross Section

No./ Nominal Diameter of Strands

Nominal Insulation Thickness

Unarmoured

Armoured

Nominal Overall Diameter

Approx. Weight

Diameter Over Inner Sheath

Armour Wire Diameter

Nominal Overall Diameter

Approx. Weight

mm2

No./mm

mm

mm

mm

mm

mm

mm

kg/km

7Cores

7x1.5

7/0.53

0.7

12.4

225

11.2

0.9

16.0

490

7x2.5

7/0.67

0.7

13.8

303

12.4

0.9

17.2

602

7x4

7/0.85

0.7

15.5

422

14.1

1.25

19.8

871

10Cores

10x1.5

7/0.53

0.7

15.6

325

14.3

1.25

20.0

761

10x2.5

7/0.67

0.7

17.5

426

15.9

1.25

21.8

943

10x4

7/0.85

0.7

19.7

597

18.5

1.25

24.4

1213

12Cores

12x1.5

7/0.53

0.7

16.2

370

14.8

1.25

20.5

827

12x2.5

7/0.67

0.7

18.1

489

16.5

1.25

22.4

1020

12x4

7/0.85

0.7

20.3

690

19.1

1.6

25.7

1462

19Cores

19x1.5

7/0.53

0.7

19.0

516

17.4

1.6

24.0

1186

19x2.5

7/0.67

0.7

21.3

725

19.9

1.6

26.7

1498

19x4

7/0.85

0.7

24.0

1037

22.6

1.6

29.4

1931

27Cores

27x1.5

7/0.53

0.7

22.7

712

21.3

1.6

28.1

1537

27x2.5

7/0.67

0.7

25.5

1004

23.9

1.6

30.9

1933

27x4

7/0.85

0.7

28.8

1445

27.2

1.6

34.4

2532

37cores

37x1.5

7/0.53

0.7

25.5

941

23.9

1.6

30.7

1856

37x2.5

7/0.67

0.7

28.7

1334

26.9

1.6

33.9

2372

37x4

7/0.85

0.7

32.5

1932

31.1

2.0

39.3

3448

48 Core

48x1.5

7/0.53

0.7

29.0

1186

27.5

1.6

34.6

2276

48x2.5

7/0.67

0.7

32.9

1706

31.3

2.0

39.6

3252

48x4

7/0.85

0.7

37.3

2479

35.7

2.0

44.2

4273

Conductor cross- sectional area

Reference Method 4 (enclosed in conduit in thermally insulating wall etc)

Reference Method 3 (enclosed in conduit on a wall or in trunking etc)

Reference Method 1 (clipped direct)

Reference Method 11 (on a perforated cable tray, horizontal or vertical)

Reference Method 12 (free air)

Horizontal flat spaced

Vertical flat spaced

Trefoil


2 cables, single- phase a.c. or d.c.

3 or 4 cables, 3-phase a.c.

2 cables, single- phase a.c. or d.c

3 or 4 cables, 3-phase a.c.

2 cables, single- phase a.c. or d.c. flat and touching

3 or 4 cables, 3-phase a.c. flat and touching or trefoil

2 cables, single- phase a.c. or d.c. or flat and touching

3 or 4 cables, 3-phase a.c. flat and touching or trefoil

2 cables, single- phase a.c. or d.c. or 3 c ables three phase

2 cables, single- phase a.c. or d.c. or 3 cables three phase

3 cables, trefoil 3-phase a.c.

1

2

3

4

5

6

7

8

9

10

11

12

mm2

A

A

A

A

A

A

A

A

A

A

A

1.5

18

17

22

19

25

23

-

-

-

-

-

2.5

24

23

30

26

34

31

-

-

-

-

-

4

33

30

40

35

46

41

-

-

-

-

-

Voltage Drop (Per Amp Per Meter)

Nominal Cross Section Area

2 cables d.c.

2 cables, single-phase a.c.

3 or 4 cables, 3-phase a.c.

Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)

Ref. Methods 1 and 11 (clipped direct or on trays touching)

Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)

Ref. Methods 1,

Ref. Methods 1 and 11

11 and 12 (in trefoil)

(Flat and touching)

1

2

3

4

5

6

7

mm2

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

1.5

31

31

27

27

27

27

2.5

19

19

16

16

16

16

4

33

12

10

10

10

10

Current-Carrying Capacities (Amp)

Conductor crosssectional area

Reference Method 1 (clipped direct)

Reference Method 11 (on a perforated horizontal cable trayor Reference Method 13 [free air] )

In single-way ducts

Laid direct in ground

one 2-core cable single phase a.c. or d.c.

one 3-core or 4-core cable 3-phase a.c.

one 2-core cable single phase a.c. or d.c.

one 3-core or 4-core cable 3-phase a.c.

one 2-core cable single phase a.c. or d.c.

one 3-core or 4-core cable 3-phase a.c.

one 2-core cable single phase a.c. or d.c.

one 3-core or 4-core cable 3-phase a.c.

1

2

3

4

5

6

7

8

9

mm2

A

A

A

A

A

A

A

A

1.5

27

23

29

25

-

23

-

28

2.5

36

31

39

33

-

30

-

36

4

49

42

52

44

-

40

-

48